Skip to content
For the complete documentation index, see llms.txt. This page is also available as Markdown.

Wiring Outputs

Hardware installation › Wiring Basics › Wiring Outputs

This page answers

  • What is an output?

  • What are the voltage and current limits?

  • What do I do if I need to switch a higher load?

  • Do the relays provide power?

How outputs work with Gallagher hardware, and their limitations.

What is an output?

A physical output can be:

  • Sirens

  • Door control

  • Control for lighting

  • Warning buzzer

  • Almost anything Gallagher needs to control can be an output

An output in Gallagher is (typically) a physical relay on a Gallagher device capable of interrupting or completing an electrical circuit.

Are there limits on the outputs?

Yes. Outputs have a maximum voltage and current they can switch. This depends on the device in question, so always refer to the install notes for the hardware in use.

Typically the limits are:

Limit
Value

Voltage

24 VDC/AC

Current load

3 A resistive, 1 A inductive (2 A resistive on the Plug In modules)

⚠️ Do not try to switch voltages higher than 24 volts (AC or DC), or a load (current draw) of over 3 amps resistive or 1 amp inductive.

What if I need to switch loads that are higher than the limits?

If you need to switch loads that are higher than these limits, install another higher rated relay that is capable of switching those loads, and drive that relay with the Gallagher relay.

Do the relays provide power?

No. They are essentially clean contacts.

The Plug In modules do have the means to have power supplied to the common of the relays. All other relays are electrically clean and isolated from all electronic circuits.