For the complete documentation index, see llms.txt. This page is also available as Markdown.

Ports by component

Ports, directions, and version-specific firewall requirements.

Ports by component

Controllers to Command Centre Server

v6.0 and higher:

Keyword
Port
Purpose

bootps

67/udp

BootP server (IP assignment, if used)

bootpc

68/udp

BootP client

HTTP

80/tcp

IE to FTController connection (web browse)

Gallagher

1072/tcp

FTController connection. Enable bi-directionally

Version behaviour: v8.50+ only needs 1072/tcp inbound from controllers. This applies once every controller uses the current server version. When any controller runs v8.40 or below, the server also needs outbound access.

v5.21 and lower:

Additionally ftp 20 & 21/tcp for software download through CCFT Server. TCP 1072 is always required. If a controller has a gateway, enable ICMP between the controller and gateway.

Clients and other components to Server

Path
Port(s)

Config Client (v7.90+)

8905/tcp (configurable)

Config Client (v7.80 and lower)

135/tcp (epmap) + DCOM 5× dynamic + 1072/udp (Intercom)

Command Centre Client

445/tcp (ClickOnce) + 4840/tcp (configurable)

Mobile Client

8901/tcp (data) + 8902/tcp (enrolment)

Gallagher Cloud (Mobile Connect)

443/tcp HTTPS outbound; DNS commandcentre-ap-southeast-2.security.gallagher.cloud

Multi-Server

4840/tcp OPCUA (configurable)

Visitor Management Client

445/tcp + 4243/tcp (configurable)

Visitor Management Kiosk

445/tcp + 4840/tcp (configurable)

Sagem/Morpho/IDEMIA biometric reader

11010/tcp (CC to reader) + 11011/tcp (secure)

Salto to Server

Port
Protocol
Direction
Purpose

1100

UDP

Server to CU

Handshake

5000–10000

UDP

CU to Server

Online controllers to server (one port per client)

5000–10000

TCP

Bi-dir

Encoders

8099

TCP

Bi-dir

Service to software (or another 8000-range port)

1433 TCP / 1434 UDP

—

Bi-dir

Editing and Database

8100 / 8101

TCP

Bi-dir

SALTO Web authentication / reporting

Do not block SaltoServiceConfigurator.exe, RWProAccessForService.exe, or HAMSForService_SQL.exe.

CU means Control Unit, such as an update point or door controller.

Controller 6000 specific

Port
Protocol
Direction
Purpose

80*

TCP

In

Tech Support Diagnostics (HTTP)

137† / 138†

UDP

In

NetBIOS-over-TCP/IP browsing

1072

TCP

In

Comms with server and other C6000s (encrypted Bertbus)

TCP-stack assigned

TCP

Out

IP Alarms (DC09, if configured); server and C6000 comms

* Port 80 opens when DIP Switch 1 is ON. † Ports 137 and 138 open when DIP Switch 6 is OFF.

  • Port 135 initiates the Client/Server connection. Port 1072 is only needed for the CC Client if intercom is required.

  • CC Camera live viewing uses a dynamically assigned camera-to-client UDP port. You cannot restrict this port.

  • Premier Client uses TCP 445 only with ClickOnce, not copied client files.

Last updated