> For the complete documentation index, see [llms.txt](https://help.security.gallagher.com/knowledge-hub/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://help.security.gallagher.com/knowledge-hub/configuration-client/licensable-features/piv-card-support/open-supervised-device-protocol-osdp-veridt-stealth-piv-readers/configuring-an-osdp-veridt-stealth-piv-reader.md).

# Configuring an OSDP Veridt Stealth PIV Reader

### Introduction

This procedure describes how to configure an Open Supervised Device Protocol (OSDP) Veridt Stealth PIV Reader in Gallagher Command Centre.

Operators require the "Edit Site" privilege in the appropriate division to be able to create, edit and delete OSDP Veridt Stealth PIV Readers.

**Note:** The "View Site" privilege in the appropriate division will allow an operator to view (but not edit) OSDP Veridt Stealth PIV Readers.

***

### Configuration

To configure an OSDP Veridt Stealth PIV Reader, perform the following procedures in Gallagher Configuration Client:

1. Click **Configure** from the menu bar, then **Hardware**.

   The **Hardware** List Window opens (in [tree view](https://help.security.gallagher.com/knowledge-hub/configuration-client/glossary-of-terms.md#tree-view)).
2. **Right click** and select **New\...OSDP Devices** > **OSDP Reader - Veridt Stealth PIV.**

   By default the **General** tab displays.
3. Complete the fields as required.

   For further detail see [General tab](https://help.security.gallagher.com/knowledge-hub/configuration-client/introduction-to-command-centre/knowing-your-way-around/generic-properties-configuration/general-tab.md).
4. Click the **Event Response** tab, and configure as required.

   For further detail see [Event Response tab](https://help.security.gallagher.com/knowledge-hub/configuration-client/introduction-to-command-centre/knowing-your-way-around/generic-properties-configuration/event-response-tab.md).
5. Click the **Alarm Instructions** tab, and configure as required.

   For further detail see [Alarm Instructions tab](https://help.security.gallagher.com/knowledge-hub/configuration-client/introduction-to-command-centre/knowing-your-way-around/generic-properties-configuration/alarm-instructions-tab.md).
6. Click each tab in turn to configure the reader:

<details>

<summary>Connections tab</summary>

1. Click the **Connections** tab.

   ![](https://3000903572-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FfCvaxj3suxNBzdwQndVT%2Fuploads%2Fgit-blob-b3c206bbd8c371819f10f665cb9e90262ff73717%2Fveridtstealthpiv_osdpreader_connectionstab.png?alt=media)

   The three fields, (i.e. **Connected to**, **RS-485 Bus** and **Device Number** ) will be populated once you assign this reader to a PIV Controller 6000. See [Assigning an OSDP Veridt Stealth PIV Reader to a Gallagher PIV Controller 6000](https://help.security.gallagher.com/knowledge-hub/configuration-client/licensable-features/piv-card-support/open-supervised-device-protocol-osdp-veridt-stealth-piv-readers/assigning-an-osdp-veridt-stealth-piv-reader-to-a-gallagher-piv-controller-6000.md) for further detail.

</details>

<details>

<summary>Advanced tab</summary>

1. Click the **Advanced** tab.

   ![](https://3000903572-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FfCvaxj3suxNBzdwQndVT%2Fuploads%2Fgit-blob-ee88131806e2a533ac741a6e28820bf08dcb3bca%2Fveridtstealthpiv_osdpreader_advancedtab.png?alt=media)
2. If you want the double-card override feature to be available, click either the **Override access zone** or the **Arm alarm zone** radio button, depending on whether you want the double-card override to override the state of the Access Zone or arm the Alarm Zone associated with the Access Zone.

   **Note:** It will only work with proximity cards. Contact will not work.
3. Configure the access mode mapping for the reader as appropriate.

   <table><thead><tr><th width="162">Field</th><th>Description</th></tr></thead><tbody><tr><td>Secure - No PIN</td><td><p>There are two options available from the drop-down, (i.e. One factor or Two factor).</p><p>Default = One factor</p></td></tr><tr><td>Secure - PIN</td><td><p>There are two options available from the drop-down, (i.e. Two factor or Three factor).</p><p>Default = Two factor</p></td></tr></tbody></table>

</details>

<details>

<summary>PIV Settings tab</summary>

1. Click the **PIV Settings** tab.

   ![](https://3000903572-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FfCvaxj3suxNBzdwQndVT%2Fuploads%2Fgit-blob-8a65e935f06e4f370655a0ba6628ab16fedf8aba%2Fveridtstealthpiv_osdpreader_pivsettingstab.png?alt=media)
2. Select the appropriate Authentication Mode by clicking the relevant radio button. By default, **Require PIV cards to contain a Card Authentication Key (CAK) certificate** is selected.

   **Notes:**

   * The authentication mode applies to PIV contactless cards only.
   * Only one authentication mode can be selected.
   * The **Allow fallback to CHUID>FASC-N authentication if card contains no CAK certificate (Not FIPS201 compliant)** option allows a reader to fallback to the CHUID> FASC-N when the PIV Card does not contain a CAK certificate, but this is not FIPS201 compliant.

</details>

<details>

<summary>Card Read Output tab</summary>

1. Click the **Card Read Output** tab.

   ![](https://3000903572-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FfCvaxj3suxNBzdwQndVT%2Fuploads%2Fgit-blob-dbca23bd4451e55a31cc91ba931a8170bef0a7ea%2Fveridtstealthpiv_osdpreader_cardreadoutputtab.png?alt=media)
2. From the **Card Read Output** drop-down list (which includes virtual outputs), select the output to switch on when a card is badged at the reader.

   **Notes:**

   * Badging a card at this reader will switch on the associated relay. The relay will then be immediately switched off unless the relay output is configured to pulse, in which case the relay will stay on for the pulse time and then be switched off. The card format does not have to be correct, nor does the card have to be assigned to a cardholder to trigger the relay.
   * It is recommended that the output be configured to pulse (via the **Advanced** tab of the Output's properties). If the Output is not configured as a pulse output then the relay will pulse for 1 second. The Output can be assigned to more than one reader at a time, each reader will cause the relay to pulse.

</details>

7. Click the **Cameras** tab if you want to associate a DVR Camera(s) with this reader.

   For further details see [Cameras tab](https://help.security.gallagher.com/knowledge-hub/configuration-client/introduction-to-command-centre/knowing-your-way-around/generic-properties-configuration/cameras-tab.md).
8. Click the **Icons** tab if you want to change the Icon Set for this reader.

   For further details regarding the **Icons** tab, see [Icons](https://help.security.gallagher.com/knowledge-hub/configuration-client/site-installation/server-properties/icons.md).
9. Click the **Custom Fields** tab if you want to add and assign a custom field value to this reader.

   For further details regarding the **Custom Fields** tab, see [Custom Fields](https://help.security.gallagher.com/knowledge-hub/configuration-client/site-installation/server-properties/custom-fields.md).
10. Click the **Notes** tab if you want to add a note(s) about this reader.

    For further details regarding the **Notes** tab, see [Notes](https://help.security.gallagher.com/knowledge-hub/configuration-client/site-installation/server-properties/notes.md).
11. Click **OK** to exit and save your changes.

    Click **Cancel** to exit without saving your changes.

    Click **Apply** to save your changes and stay in this window.

#### Assigning the Reader

Once the configuration work is complete, you need to assign the Reader to a Gallagher PIV Controller 6000 and a Door.

12. Assign this reader to a PIV Controller 6000. See [Assigning an OSDP Veridt Stealth PIV Reader to a Gallagher PIV Controller 6000](https://help.security.gallagher.com/knowledge-hub/configuration-client/licensable-features/piv-card-support/open-supervised-device-protocol-osdp-veridt-stealth-piv-readers/assigning-an-osdp-veridt-stealth-piv-reader-to-a-gallagher-piv-controller-6000.md) for further detail.
13. From the Door List Window, highlight the door you want to assign this reader to.
14. **Right click** and select **Properties**.
15. Click the **Entry Zone** or **Exit Zone** tab as appropriate.
16. Assign the reader to the appropriate Reader Address by selecting it from the relevant **Reader(s)** drop-down list.

    ![](https://3000903572-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FfCvaxj3suxNBzdwQndVT%2Fuploads%2Fgit-blob-bfb3899906cacc04fbc7d2f14e5179c65332830d%2Fveridtstealthpiv_osdp_door_entryzonetab.png?alt=media)
17. If the reader is set to dual authentication/escort+visitor or double card override, click the **Advanced** tab and increase the **Second card (for two-card entry) must be swiped within** value above 30 seconds.
18. Click **OK** to exit and save your changes.

    Click **Cancel** to exit without saving your changes.

    Click **Apply** to save your changes and stay in this window.

### Result

An OSDP Veridt Stealth PIV Reader has been configured.

**Notes:**

* The Veridt Readers capacity displays on the **Status and Overrides** tab. For example, the status message below indicates that the reader supports Biometrics.

  ![](https://3000903572-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FfCvaxj3suxNBzdwQndVT%2Fuploads%2Fgit-blob-eb988ee8d40ecbafa65b9a5f7b63ee62d643ba3f%2F36546.png?alt=media)
* An OSDP HID Reader or non-Veridt Reader assigned to the Veridt Reader FT Item will have the status message *"The OSDP device is not a Veridt Reader"* (on the **Status and Overrides** tab), or it could go offline.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://help.security.gallagher.com/knowledge-hub/configuration-client/licensable-features/piv-card-support/open-supervised-device-protocol-osdp-veridt-stealth-piv-readers/configuring-an-osdp-veridt-stealth-piv-reader.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.