> For the complete documentation index, see [llms.txt](https://help.security.gallagher.com/knowledge-hub/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://help.security.gallagher.com/knowledge-hub/configuration-client/integrated-systems/salto-lock-interface/space-site-configuration/emergency-opening.md).

# Emergency Opening

### Introduction

This procedure describes how to perform an emergency opening. This may be necessary if the battery for a door electronic lock goes flat.

### Procedure

1. Connect the PPD to the Salto server.
2. On the PPD, switch the **Power** button on.

   The screen on the PPD displays the main menu with the options available.
3. In the Salto application, select **System > PPD**.

   The PPD information screen is displayed.

   ![](https://3000903572-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FfCvaxj3suxNBzdwQndVT%2Fuploads%2Fgit-blob-5fc669e8f7fb36ae6f0e284bc3163125a36bb0e0%2Fppdconnection.png?alt=media)
4. Select the checkbox of the access point for which you want to perform the emergency opening.

   You can select more than one access point if required. However, you cannot select access points with different calendars; multiple selections must be controlled by the same calendar.
5. Select the **Allow emergency opening** checkbox in the Actions To Do panel.

   The checkbox is greyed out if you have set emergency opening as a default option in the General options. Otherwise, you must select it each time you want to perform an emergency opening.
6. Type a password for the emergency opening in the **Password** field, if required. If you type a password, you must enter this password in the PPD before you can perform the emergency opening. If a password is not entered, the PPD could be misused, if in the possession of an unauthorised person, to open all doors on site.

   **Notes:**

   * Your PPD firmware must be version 01.29 or higher to use this option.
   * The password can only contain digits.
   * The **Password** field is greyed out if you have set emergency opening as a default option in the General options and entered a password there already for the option
   * If the **Password** field is left blank, no password will be required for emergency openings (not recommended).
7. Click the **Download** button.

   The PPD progress screen is displayed.
8. Wait for the download to complete.

   A pop-up is displayed confirming that the operation was completed successfully.
9. Click the **OK** button.

   You can now use the PPD to perform an emergency opening of the selected access point by selecting **Emergency Opening** in the PPD’s menu and connecting the PPD to the lock.
10. Insert the 3 pins cable into the lock reader. You will hear the lock engine sound, and in a few seconds the door is ready to be opened. The message *"Door open, room number"* displays on the PPD.

    **Note:** If a password has been set, before the PPD will open the door, you will be prompted to enter the password. The PPD will display the message *"Insert password"*. Using the up and down arrows look for the digits of the password. When found click the **OK** key and the digit will be replaced by a star. Look for the next digit of the password using the same process. Once the last digit of the password has been introduced, click the **OK** key and the door will open.

    If the reason you had to use the PPD for an emergency opening is that the door's batteries have gone flat, then it is recommended that you replace lock batteries of the newly opened door immediately. Salto locks are equipped with three alkaline batteries, depending on which lock type you purchase, (i.e. LR03 AAA, 1.5 V model). After battery replacement, you must update the electronic lock with the PPD, as the internal clock stopped and the Time Zones and Calendar settings were lost when the batteries ran out.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://help.security.gallagher.com/knowledge-hub/configuration-client/integrated-systems/salto-lock-interface/space-site-configuration/emergency-opening.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.