> For the complete documentation index, see [llms.txt](https://help.security.gallagher.com/knowledge-hub/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://help.security.gallagher.com/knowledge-hub/configuration-client/appendices/ccc-identifiers.md).

# CCC Identifiers

### Introduction

This topic provides a list of what **CCC** will be sent when a particular **XYZ** event occurs. Each **XYZ** event below is listed in a table with its data type. There are two data types, as follows:

* ZONE: this means that the Hardware **CCC** is used, and
* USER: this means that the User **CCC** is used.

**Note:**

In the case of Panic Alarms, (i.e. Duress messages), if there is a reader on a door, Contact ID sends the Door's CCC code rather than the Reader's CCC code.

***

### ALARMS

#### Medical Alarms - 100

| XYZ event              | Data type |
| ---------------------- | --------- |
| 100 Medical            | ZONE      |
| 101 Personal Emergency | ZONE      |
| 102 Fail to report in  | ZONE      |

#### Fire Alarms - 110

| XYZ event        | Data type |
| ---------------- | --------- |
| 110 Fire         | ZONE      |
| 111 Smoke        | ZONE      |
| 112 Combustion   | ZONE      |
| 113 Water flow   | ZONE      |
| 114 Heat         | ZONE      |
| 115 Pull Station | ZONE      |
| 116 Duct         | ZONE      |
| 117 Flame        | ZONE      |
| 118 Near Alarm   | ZONE      |

#### Panic Alarms - 120

| XYZ event                   | Data type |
| --------------------------- | --------- |
| 120 Panic                   | ZONE      |
| 121 Duress                  | USER      |
| 122 Silent                  | ZONE      |
| 123 Audible                 | ZONE      |
| 124 Duress - Access granted | ZONE      |
| 125 Duress - Egress granted | ZONE      |

#### Burglar Alarms - 130

| XYZ event              | Data type |
| ---------------------- | --------- |
| 130 Burglary           | ZONE      |
| 131 Perimeter          | ZONE      |
| 132 Interior           | ZONE      |
| 133 24 Hour (Safe)     | ZONE      |
| 134 Entry/Exit         | ZONE      |
| 135 Day/night          | ZONE      |
| 136 Outdoor            | ZONE      |
| 137 Tamper             | ZONE      |
| 138 Near alarm         | ZONE      |
| 139 Intrusion Verifier | ZONE      |

#### General Alarm - 140

| XYZ event                      | Data type |
| ------------------------------ | --------- |
| 140 General Alarm              | ZONE      |
| 141 Polling loop open          | ZONE      |
| 142 Polling loop short         | ZONE      |
| 143 Expansion module failure   | ZONE      |
| 144 Sensor tamper              | ZONE      |
| 145 Expansion module tamper    | ZONE      |
| 146 Silent Burglary            | ZONE      |
| 147 Sensor Supervision Failure | ZONE      |

#### 24 Hour Non-Burglary - 150 and 160

| XYZ event                    | Data type |
| ---------------------------- | --------- |
| 150 24 Hour Non-Burglary     | ZONE      |
| 151 Gas detected             | ZONE      |
| 152 Refrigeration            | ZONE      |
| 153 Loss of heat             | ZONE      |
| 154 Water Leakage            | ZONE      |
| 155 Foil Break               | ZONE      |
| 156 Day Trouble              | ZONE      |
| 157 Low bottled gas level    | ZONE      |
| 158 High temp                | ZONE      |
| 159 Low temp                 | ZONE      |
| 161 Loss of air flow         | ZONE      |
| 162 Carbon Monoxide detected | ZONE      |
| 163 Tank level               | ZONE      |

#### Fire Supervisory - 200 and 210

| XYZ event              | Data type |
| ---------------------- | --------- |
| 200 Fire Supervisory   | ZONE      |
| 201 Low water pressure | ZONE      |
| 202 Low CO2            | ZONE      |
| 203 Gate valve sensor  | ZONE      |
| 204 Low water level    | ZONE      |
| 205 Pump activated     | ZONE      |
| 206 Pump failure       | ZONE      |

#### System Troubles - 300 and 310

| XYZ event                     | Data type |
| ----------------------------- | --------- |
| 300 System Trouble            | ZONE      |
| 301 AC Loss                   | ZONE      |
| 302 Low system battery        | ZONE      |
| 303 RAM Checksum bad          | ZONE      |
| 304 ROM Checksum bad          | ZONE      |
| 305 System reset              | ZONE      |
| 306 Panel programming changed | ZONE      |
| 307 Self-test failure         | ZONE      |
| 308 System shutdown           | ZONE      |
| 309 Battery test failure      | ZONE      |
| 310 Ground fault              | ZONE      |
| 311 Battery Missing/Dead      | ZONE      |
| 312 Power Supply Overcurrent  | ZONE      |
| 313 Engineer Reset            | USER      |

#### Sounder / Relay Troubles - 320

| XYZ event                          | Data type |
| ---------------------------------- | --------- |
| 320 Sounder/Relay                  | ZONE      |
| 321 Bell 1                         | ZONE      |
| 322 Bell 2                         | ZONE      |
| 323 Alarm relay                    | ZONE      |
| 324 Trouble relay                  | ZONE      |
| 325 Reversing relay                | ZONE      |
| 326 Notification Appliance Ckt. #3 | ZONE      |
| 327 Notification Appliance Ckt. #4 | ZONE      |

#### System Peripheral Trouble - 330 and 340

| XYZ event                      | Data type |
| ------------------------------ | --------- |
| 330 System Peripheral trouble  | ZONE      |
| 331 Polling loop open          | ZONE      |
| 332 Polling loop short         | ZONE      |
| 333 Expansion module failure   | ZONE      |
| 334 Repeater failure           | ZONE      |
| 335 Local printer out of paper | ZONE      |
| 336 Local printer failure      | ZONE      |
| 337 Exp. Module DC Loss        | ZONE      |
| 338 Exp. Module Low Batt.      | ZONE      |
| 339 Exp. Module Reset          | ZONE      |
| 341 Exp. Module Tamper         | ZONE      |
| 342 Exp. Module AC Loss        | ZONE      |
| 343 Exp. Module self-test fail | ZONE      |
| 344 RF Receiver Jam Detect     | ZONE      |

#### Communication Troubles - 350 and 360

| XYZ event                          | Data type |
| ---------------------------------- | --------- |
| 350 Communication trouble          | ZONE      |
| 351 Telco 1 fault                  | ZONE      |
| 352 Telco 2 fault                  | ZONE      |
| 353 Long Range Radio xmitter fault | ZONE      |
| 354 Failure to communicate event   | ZONE      |
| 355 Loss of Radio supervision      | ZONE      |
| 356 Loss of central polling        | ZONE      |
| 357 Long Range Radio VSWR problem  | ZONE      |

#### Protection Loop - 370

| XYZ event                   | Data type |
| --------------------------- | --------- |
| 370 Protection loop         | ZONE      |
| 371 Protection loop open    | ZONE      |
| 372 Protection loop short   | ZONE      |
| 373 Fire trouble            | ZONE      |
| 374 Exit error alarm (zone) | ZONE      |
| 375 Panic zone trouble      | ZONE      |
| 376 Hold-up zone trouble    | ZONE      |
| 377 Swinger Trouble         | ZONE      |
| 378 Cross-zone Trouble      | ZONE      |

#### Sensor Trouble - 380

| XYZ event                              | Data type |
| -------------------------------------- | --------- |
| 380 Sensor trouble                     | ZONE      |
| 381 Loss of supervision - RF           | ZONE      |
| 382 Loss of supervision - RPM          | ZONE      |
| 383 Sensor tamper                      | ZONE      |
| 384 RF Low battery                     | ZONE      |
| 385 Smoke detector Hi sensitivity      | ZONE      |
| 386 Smoke detector Low sensitivity     | ZONE      |
| 387 Intrusion detector Hi sensitivity  | ZONE      |
| 388 Intrusion detector Low sensitivity | ZONE      |
| 389 Sensor self-test failure           | ZONE      |
| 391 Sensor Watch trouble               | ZONE      |
| 392 Drift Compensation Error           | ZONE      |
| 393 Maintenance Alert                  | ZONE      |

***

### OPEN/CLOSE/REMOTE ACCESS

#### Open/Close - 400, 440, 450

| XYZ event                                        | Data type |
| ------------------------------------------------ | --------- |
| 400 Open/Close                                   | USER      |
| 401 O/C by user                                  | USER      |
| 402 Group O/C                                    | USER      |
| 403 Automatic O/C                                | USER      |
| 404 Late to O/C (*Note:* Use 453, 454 instead)   | USER      |
| 405 Deferred O/C (*Note:* Obsolete - do not use) | USER      |
| 406 Cancel                                       | USER      |
| 407 Remote arm/disarm                            | USER      |
| 408 Quick arm                                    | USER      |
| 409 Keyswitch O/C                                | USER      |
| 441 Armed STAY                                   | USER      |
| 442 Keyswitch Armed STAY                         | USER      |
| 450 Exception O/C                                | USER      |
| 451 Early O/C                                    | USER      |
| 452 Late O/C                                     | USER      |
| 453 Failed to Open                               | USER      |
| 454 Failed to Close                              | USER      |
| 455 Auto-arm Failed                              | USER      |
| 456 Partial Arm                                  | USER      |
| 457 Exit Error (user)                            | USER      |
| 458 User on Premises                             | USER      |
| 459 Recent Close                                 | USER      |
| 461 Wrong Code Entry                             | USER      |
| 462 Legal Code Entry                             | USER      |
| 463 Re-arm after Alarm                           | USER      |
| 464 Auto-arm Time Extended                       | USER      |
| 465 Panic Alarm Reset                            | ZONE      |
| 466 Service On/Off Premises                      | USER      |

#### Remote Access - 410

| XYZ event                             | Data type |
| ------------------------------------- | --------- |
| 411 Callback request made             | USER      |
| 412 Successful download/access        | USER      |
| 413 Unsuccessful access               | USER      |
| 414 System shutdown command received  | USER      |
| 415 Dialler shutdown command received | USER      |
| 416 Successful Upload                 | ZONE      |

#### Access control - 420 and 430

| XYZ event                                    | Data type |
| -------------------------------------------- | --------- |
| 421 Access denied                            | USER      |
| 422 Access report by user                    | USER      |
| 423 Forced Access                            | ZONE      |
| 424 Egress Denied                            | USER      |
| 425 Egress Granted                           | USER      |
| 426 Access Door propped open                 | ZONE      |
| 427 Access point Door Status Monitor trouble | ZONE      |
| 428 Access point Request To Exit trouble     | ZONE      |
| 429 Access program mode entry                | USER      |
| 430 Access program mode exit                 | USER      |
| 431 Access threat level change               | USER      |
| 432 Access relay/trigger fail                | ZONE      |
| 433 Access RTE shunt                         | ZONE      |
| 434 Access DSM shunt                         | ZONE      |

***

### BYPASSES / DISABLES

#### System Disables - 500 and 510

| XYZ event                 | Data type |
| ------------------------- | --------- |
| 501 Access reader disable | ZONE      |

#### Sounder / Relay Disables - 520

| XYZ event                                  | Data type |
| ------------------------------------------ | --------- |
| 520 Sounder/Relay Disable                  | ZONE      |
| 521 Bell 1 disable                         | ZONE      |
| 522 Bell 2 disable                         | ZONE      |
| 523 Alarm relay disable                    | ZONE      |
| 524 Trouble relay disable                  | ZONE      |
| 525 Reversing relay disable                | ZONE      |
| 526 Notification Appliance Ckt. #3 disable | ZONE      |
| 527 Notification Appliance Ckt. #4 disable | ZONE      |

#### System Peripheral Disables - 530 and 540

| XYZ event          | Data type |
| ------------------ | --------- |
| 531 Module Added   | ZONE      |
| 532 Module Removed | ZONE      |

#### Communication Disables - 550 and 560

| XYZ event                           | Data type |
| ----------------------------------- | --------- |
| 551 Dialler disabled                | ZONE      |
| 552 Radio transmitter disabled      | ZONE      |
| 553 Remote Upload/Download disabled | ZONE      |

#### Bypasses - 570

| XYZ event               | Data type |
| ----------------------- | --------- |
| 570 Zone/Sensor bypass  | ZONE      |
| 571 Fire bypass         | ZONE      |
| 572 24 Hour zone bypass | ZONE      |
| 573 Burg. bypass        | ZONE      |
| 574 Group bypass        | USER      |
| 575 Swinger bypass      | ZONE      |
| 576 Access zone shunt   | ZONE      |
| 577 Access point bypass | ZONE      |

***

### TEST / MISC.

#### Test/Misc. - 600 and 610

| XYZ event                                  | Data type |
| ------------------------------------------ | --------- |
| 601 Manual trigger test report             | ZONE      |
| 602 Periodic test report                   | ZONE      |
| 603 Periodic RF transmission               | ZONE      |
| 604 Fire test                              | USER      |
| 605 Status report to follow                | ZONE      |
| 606 Listen-in to follow                    | ZONE      |
| 607 Walk test mode                         | USER      |
| 608 Periodic test - System Trouble Present | ZONE      |
| 609 Video Xmitter active                   | ZONE      |
| 611 Point tested OK                        | ZONE      |
| 612 Point not tested                       | ZONE      |
| 613 Intrusion Zone Walk Tested             | ZONE      |
| 614 Fire Zone Walk Tested                  | ZONE      |
| 615 Panic Zone Walk Tested                 | ZONE      |
| 616 Service Request                        | ZONE      |

#### Event Log - 620

| XYZ event                    | Data type |
| ---------------------------- | --------- |
| 621 Event Log reset          | ZONE      |
| 622 Event Log 50% full       | ZONE      |
| 623 Event Log 90% full       | ZONE      |
| 624 Event Log overflow       | ZONE      |
| 625 Time/Date reset          | USER      |
| 626 Time/Date inaccurate     | ZONE      |
| 627 Program mode entry       | ZONE      |
| 628 Program mode exit        | ZONE      |
| 629 32 Hour Event log marker | ZONE      |

#### Scheduling - 630

| XYZ event                     | Data type |
| ----------------------------- | --------- |
| 630 Schedule change           | ZONE      |
| 631 Exception schedule change | ZONE      |
| 632 Access schedule change    | ZONE      |

#### Personal Monitoring - 640

| XYZ event                 | Data type |
| ------------------------- | --------- |
| 641 Senior Watch Trouble  | ZONE      |
| 642 Latch-key Supervision | USER      |

#### Misc. - 650

| XYZ event                   | Data type |
| --------------------------- | --------- |
| 651 Reserved for Ademco Use | ZONE      |
| 652 Reserved for Ademco Use | USER      |
| 653 Reserved for Ademco Use | USER      |
| 654 System Inactivity       | ZONE      |


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://help.security.gallagher.com/knowledge-hub/configuration-client/appendices/ccc-identifiers.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.